KYORITSU Earth Testers  	4102A
    
    
                
    
        
 Pengiriman :
 3 hari sejak pembayaran
 
 Lokasi :
  Jawa Barat - Bekasi
 
 Update Terakhir :
 11-02-2016 13:52
 
Dapatkan Spesifikasi Harga 
KYORITSU Earth Testers  	4102A Produk Terbaik dari
ANDALAN PRIMA SEJAHTERA  LABORATORY EQUIPMENT, CHEMICAL, GLASWARE, MEASURING AND TEST
 
       
        
         
 
    
        
Detail Produk
    
    
         
    
        
            
            
                
                    
                        
                        
                            
                                
                                    | 4102A | 
                                    Soft Case Model | 
                                 
                                
                                    | 4102A-H | 
                                    Hard Case Model | 
                                 
                            
                         
                         | 
                        
                         Product Catalogue  
                         | 
                     
                
             
             | 
        
        
            |   | 
            
            
                
                    
                         
                        
                            
                                
                                    | • | 
                                    The latest circuit design permits the instrument to operate with the minimum of influence from earth voltage and earth resistance of auxiliary earth spikes. | 
                                 
                                
                                    | • | 
                                    Dust and drip proof. (designed to IEC 529 IP54) | 
                                 
                                
                                    | • | 
                                    Earth resistance value can be read directly from the scale. | 
                                 
                                
                                    | • | 
                                    Designed to meet IEC 61010-1 safety standard. | 
                                 
                                
                                    | • | 
                                    Capable of measuring earth voltage. | 
                                 
                                
                                    | • | 
                                    Small and lightweight. Shock resistant new case material. | 
                                 
                                
                                    | • | 
                                    2mA measuring current permits earth resistance tests without tripping earth leakage current breakers in the circuit under test. | 
                                 
                                
                                    | • | 
                                    Lead wire connection to C and P terminals and proper auxiliary earth resistance can be checked by "OK" lamp. Lead wire connection to C and E terminals is good when "OK" lamp is illuminated. | 
                                 
                            
                         
                         | 
                          
                          
                          | 
                     
                    
                        | 
                        
                         | 
                        
                        
                         | 
                     
                    
                        | 
                         4102A Soft Case Model 
                         | 
                        
                         4102A-H Hard Case Model 
                         | 
                     
                
             
             | 
        
        
              | 
        
        
            |   | 
            
            
                
                    
                        
                        
                            
                                
                                    Measurement 
                                    Ranges | 
                                    Earth Resistance: 0 - 12 Ω/0 - 120 Ω/0 - 1200 Ω 
                                    Earth Voltage [50,60Hz]: 0 - 30V AC | 
                                 
                                
                                    | Accuracy | 
                                    Earth Resistance: ±3% of full scale 
                                    Earth Voltage: ±3% of full scale | 
                                 
                                
                                    | Overload Protection | 
                                    Earth Resistance: 276V AC for 10 seconds 
                                    across 2 of the 3 terminals 
                                    Earth Voltage: 276V AC for 1 minute | 
                                 
                                
                                    | Safety Standard | 
                                    IEC 61010-1 CAT III 300V Pollution Degree 2, IEC 61557 | 
                                 
                                
                                    | Applicable Standards | 
                                    IEC 60529 IP54 | 
                                 
                                
                                    | Withstand Voltage | 
                                    3700V AC for 1 minute | 
                                 
                                
                                    | Power Source | 
                                    R6 (AA) (1.5V) × 6 | 
                                 
                                
                                    | Dimensions | 
                                    105(L) × 158(W) × 70(D)mm | 
                                 
                                
                                    | Weight | 
                                    600g approx. | 
                                 
                                
                                    | Accessories | 
                                    7095A (Earth resistance test leads) × 1set 
                                    (red-20m, yellow-10m, green-5m) 
                                    8032 (Auxiliary earth spikes) × 1set 
                                    7127A (Simplified measurement probe) × 1set 
                                    R6 (AA) × 6 
                                    Neck strap 
                                    Instruction Manual 
                                    
                                        
                                            
                                                | Carrying Case | 
                                                : 9084 (Soft case) | 
                                             
                                            
                                                |   | 
                                                : 9164 (Hard case) | 
                                             
                                        
                                     
                                     | 
                                 
                                
                                    | Optional | 
                                    
                                     7100A (Precision measurement cord set) 
                                      
                                     | 
                                 
                            
                         
                         | 
                     
                
             
             |