Key Specifications
| Description |
Liquid-to-Air Cooler, Turbine Pump |
|---|---|
| Working Temperature Range °C |
Ambient +5° to 70°C
|
| Pump Type |
Turbine
|
Key Features
- An economical solution for applications where cooling fluid temperature is higher than ambient and temperature control is not required
- Quiet liquid-to-air cooling
- Positive displacement or turbine pump
- Built-in low liquid level indicator
Related Fluids & Accessories
Common Specifications
| Working Temperature Range °F |
Ambient +10° to 158°
|
|---|---|
| Working Temperature Range °C |
Ambient +5° to 70°C
|
| Reservoir Capacity (gallons) |
1.11
|
| Reservoir Capacity (liters) |
4.2
|
| Reservoir Cover |
Screw-on Cap
|
| Cleanable Air Filter |
Yes
|
| Cleanable Fluid Filter |
Yes
|
| Pump Type |
Turbine
|
| Pump Speed |
Constant, Single Speed
|
| Process Connections |
1/2" (F) NPT
|
| Reservoir Liquid Level Indicator |
Yes
|
| Reservoir Drain |
Yes
|
| Maximum Ambient Temperature °F |
95°
|
| Maximum Ambient Temperature °C |
35°
|
| Overall Dimensions (L x W x H) (inches) |
20.5 x 15 x 22.3 in
|
| Overall Dimensions (L x W x H) (cm) |
52 x 38.1 x 54.6 cm
|
| Shipping Weight (pounds) |
132.0
|
| Shipping Weight (kilograms) |
59.9
|
| Catalog Page Number |
107
|
60 Hz Only
| Part Number |
3370TBA11B
|
|---|---|
| Maximum Pressure (psi) |
62.0
|
| Maximum Pressure (bar) | |
| Maximum Pressure Flow Rate (gpm) |
5.40
|
| Maximum Pressure Flow Rate (l/min) |
20.5
|
| Cooling Capacity @ 20°C (W) |
500 based on 2°C ΔT
1000 based on 4°C ΔT
2000 based on 8°C ΔT
3000 based on 10°C ΔT
4000 based on 11°C ΔT
ΔT = Process water temperature - ambient air temperature
|
| Included Hardware |
Two sets of Inlet/Outlet Adapters: ½ inch male NPT, 5/8 inch male NPT
|
| Electrical Requirements (VAC/Hz/Ph/A) |
120/60/1/5.5
|
| Regulatory Approvals |
TUV
|
50 Hz Only
| Part Number |
3370TBA12E
|
|---|---|
| Maximum Pressure (psi) |
50.0
|
| Maximum Pressure (bar) | |
| Maximum Pressure Flow Rate (gpm) |
4.50
|
| Maximum Pressure Flow Rate (l/min) |
17.1
|
| Cooling Capacity @ 20°C (W) |
500 based on 2°C ΔT
1000 based on 4°C ΔT
2000 based on 8°C ΔT
3000 based on 10°C ΔT
4000 based on 11°C ΔT
ΔT = Process water temperature - ambient air temperature
|
| Included Hardware |
Two sets of Inlet/Outlet Adapters: ½ inch male NPT, 5/8 inch male NPT
|
| Electrical Requirements (VAC/Hz/Ph/A) |
240/50/1/3
|
| Regulatory Approvals |
CE
|