Key Specifications
Description |
Liquid-to-Air Cooler, Positive Displacement Pump |
---|---|
Working Temperature Range °C |
Ambient +5° to 70°C
|
Pump Type |
Positive Displacement
|
Key Features
- An economical solution for applications where cooling fluid temperature is higher than ambient and temperature control is not required
- Quiet liquid-to-air cooling
- Positive displacement or turbine pump
- Built-in low liquid level indicator
Related Fluids & Accessories
Common Specifications
Working Temperature Range °F |
Ambient +10° to 158°
|
---|---|
Working Temperature Range °C |
Ambient +5° to 70°C
|
Reservoir Capacity (gallons) |
1.11
|
Reservoir Capacity (liters) |
4.2
|
Reservoir Cover |
Screw-on Cap
|
Cleanable Air Filter |
Yes
|
Cleanable Fluid Filter |
Yes
|
Pump Type |
Positive Displacement
|
Pump Speed |
Constant, Single Speed
|
Process Connections |
1/2" (F) NPT
|
Reservoir Liquid Level Indicator |
Yes
|
Reservoir Drain |
Yes
|
Maximum Ambient Temperature °F |
95°
|
Maximum Ambient Temperature °C |
35°
|
Overall Dimensions (L x W x H) (inches) |
20.5 x 15 x 22.3 in
|
Overall Dimensions (L x W x H) (cm) |
52 x 38.1 x 54.6 cm
|
Shipping Weight (pounds) |
132.0
|
Shipping Weight (kilograms) |
59.9
|
Catalog Page Number |
107
|
60 Hz Only
Part Number |
3370P9A11B
|
---|---|
Maximum Pressure (psi) |
100.0
|
Maximum Pressure (bar) | |
Maximum Pressure Flow Rate (gpm) |
2.40
|
Maximum Pressure Flow Rate (l/min) |
9.1
|
Cooling Capacity @ 20°C (W) |
500 based on 2°C ΔT
1000 based on 4°C ΔT
2000 based on 8°C ΔT
3000 based on 10°C ΔT
4000 based on 11°C ΔT
ΔT = Process water temperature - ambient air temperature
|
Included Hardware |
Two sets of Inlet/Outlet Adapters: ½ inch male NPT, 5/8 inch male NPT
|
Electrical Requirements (VAC/Hz/Ph/A) |
120/60/1/5.5
|
Regulatory Approvals |
TUV
|
50 Hz Only
Part Number |
3370P9A12E
|
---|---|
Maximum Pressure (psi) |
100.0
|
Maximum Pressure (bar) | |
Maximum Pressure Flow Rate (gpm) |
2.00
|
Maximum Pressure Flow Rate (l/min) |
7.6
|
Cooling Capacity @ 20°C (W) |
500 based on 2°C ΔT
1000 based on 4°C ΔT
2000 based on 8°C ΔT
3000 based on 10°C ΔT
4000 based on 11°C ΔT
ΔT = Process water temperature - ambient air temperature
|
Included Hardware |
Two sets of Inlet/Outlet Adapters: ½ inch male NPT, 5/8 inch male NPT
|
Electrical Requirements (VAC/Hz/Ph/A) |
240/50/1/3
|
Regulatory Approvals |
CE
|